Description Packg. * Code
ALIZÉ AUTO TEMPO 20/75 m³/h 230V elec. 12 2051
ALIZÉ AUTO TEMPO 30/90 m³/h 230V elec. 12 2052
ALIZÉ AUTO TEMPO 45/105 m³/h 230V elec. 12 2053
ALIZÉ AUTO TEMPO 45/120 m³/h 230V electric 12 2054
ALIZÉ AUTO TEMPO 45/135 m³/h 230V electric 12 2055
Accessories
Open/close pushbutton for elec. operation (230V or batteries) 18 1790
* packaged quantities are shown for information purposes – All items can be ordered singly
ALIZÉ AUTO TEMPO 20/75 m³/h 230V elec.

Open/close pushbutton for elec. operation (230V or batteries)more information




APARTMENT BLOCKS

- Kitchens: ALIZÉ AUTO and ALIZÉ AUTO TEMPO dual flowrate vents provide a predetermined extraction rate (“trickle”) at a pressure head of between 50 and 160Pa and a boost extraction rate turned on and (on the ALIZE AUTO  vent) off by the user.

ALIZÉ AUTO TEMPO vents come in three models for each flowrate:

ALIZÉ AUTO TEMPO cord: opening and closing by pull cord

ALIZÉ AUTO TEMPO elec: opening and closing by pushbutton, 230V power supply

ALIZÉ AUTO TEMPO battery: activation by pushbutton, 3 x 1.5V battery operated

- Bathrooms and WCs: the ALIZÉ AUTO single flowrate vent  provides a predetermined extraction rate at a pressure head of between 50 and 160Pa.

 

OFFICE PREMISES

The ALIZÉ AUTO single flowrate vent provides a predetermined extraction rate at a pressure head of between 50 and 160Pa.

ALIZÉ AUTO dual flowrate vents are intended for kitchen installation.

In addition to the general installation guidelines (see general information tab), the 230VAC power supply to the vent must be via a recessed 2-wire cable (2 x 1.5 mm²) leading to the back of the support plate (diagram opposite). This power supply must include a suitable protection device and be identified on the main distribution board in order to facilitate maintenance or repair of the vent.
Class 2 electrical appliance.

The vent must always be screwed to the wall or ceiling via the 3 holes provided for this purpose on the plate.

CETIAT test reports No.1114119 
 ALIZE AUTO
TEMPO
Lw in dB(A)  Dn,e,w (C) in dB
 70 Pa 100 Pa 136 Pa

160 Pa

 

 20/75 m3/h  24 29 33 36 55
 30/90 m3/h 25 29 35 37 53
 45/135 m3/h 31 34 38 39 53
Values taken from
CETIAT test reports

 Certified values

For 45/105 and 45/120 flowrates, use values for 45/135 vent.