Extraction vents Combustion gas ventilation system
THERMOGAZ

THERMOGAZ - Defaut

< Back to Extraction vents - Combustion gas ventilation system
Description Packg. * Code
Thermogaz 20/75/100 m³/hour 23 kW CC 118 20 2701
Thermogaz 30/90/100 m³/hour 23 kW CC 118 20 2702
Thermogaz 45/105/100 m³/hour 23 kW CC 118 20 2703
Thermogaz 45/120/100 m³/hour 23 kW CC 118 20 2713
Thermogaz 45/135/100 m³/hour 23 kW CC 118 20 2705
Thermogaz Ø 116, 23 kW CC 118 20 -116
Thermogaz VMCI, 23 kW CC 118 20 VMCI
Thermogaz 20/75/100 m³/hour, 23 kW CC125 20 2710
Thermogaz 30/90/100 m³/hour, 23 kW CC125 20 2711
Thermogaz 45/105/100 m³/hour, 23 kW CC125 20 2712
Thermogaz 45/120/100 m³/hour, 23 kW CC125 20 2713
Thermogaz 45/135/100 m³/hour, 23 kW CC125 20 2714
Thermogaz Ø 116, 23 kW CC 125 20 -116
Thermogaz VMCI, 23 kW CC 125 20 VMCI
Accessories
Cord guide for cord-operated ceiling vents 10 1791
* packaged quantities are shown for information purposes – All items can be ordered singly
Thermogaz 20/75/100 m³/hour 23 kW CC 118

Cord guide for cord-operated ceiling ventsmore information



THERMOGAZ kitchen extraction vents, designed for connecting gas boilers with a 23kW heat ouput (*see manufacturer’s instructions for higher outputs) to the ventilation network, provide a continuous self-regulated extraction (“trickle”), a manually activated boost, and an additional flowrate slaved to the boiler operation. Operating range 80–140Pa.

Vent components: 

  Aluminium body
  Bimetallic actuators
  Flap
  Drawer
  Boiler connection adapter
  Duct connection adapter
  Seal
  Pull-cord operation
  Boost-on indicator

ON VERTICAL WALLS

Plug-in fit to extraction duct Ø125 (or 116).
The unit is held in place and kept airtight by a lip seal.

The vent is linked to the boiler by a special aluminium branch duct Ø118 or 125mm interior.




ON CEILINGS (in houses)

The THERMOGAZ VMCI assembly comprises a Thermogaz vent, a metal sleeve Ø125 x length 250mm, and a cord guide. This ceiling mounted configuration allows a boiler to be connected to a gas extractor in a house.


 

CETIAT test report 9580056; CSTB test report 713-950-0068


Trickle and maximum extraction rates at 20°C



The vents are characterized by

- their acoustic power levels Lw with trickle extraction

- their normalized acoustic insulation Dn,e,w (C) measured per the specifications of standard E 51-711.



Boiler extraction flowrate





 THERMOGAZ Lw in dB(A)  Dn,e,w (C) in dB
 80Pa 100Pa 130Pa
20/75m3/h  31 35 38 58
30/90m3/h 30 34 37 57
45/105m3/h 33 36 39 56
45/135m3/h  33 36 39 56

The amended directive of 25th April, 1985 (France) obliges owners (or joint-property managers in the case of apartment blocks) of buildings with ventilation systems that handle combustion gases to sign a contract for yearly maintenance of their ventilation network/gas appliances and for a 5-yearly thorough inspection of all the installations.

Remove the duct that links to the boiler, remove the boiler connection adapter by unscrewing the 3 fastening screws, and remove the drawer holding the bimetallic actuator and damper flap. Clean the airway and the drawer-flap assembly thoroughly, without dismantling any of the mechanism. Now fit the drawer-flap assembly back into the vent body and refit the adapter using the 3 screws.